Technical characteristics
*Product Number (SKU) PCS020Y4IP20U
PCS020Y4IP20P
PCS030Y4IP30U
PCS030Y4IP20P
PCS045Y4IP20U
PCS0454YIP20P
PCS060Y4IP20U
PCS060Y4IP20P
PCS090Y4IP20U
PCS090Y4IP20P
PCS120Y4IP20U
PCS120Y4IP20P
Compensation capacity per phase 20 A rms 30 A rms 45 A rms 60 A rms 90 A rms 120 A rms
Maximum compensation capacity in
the neutral 60 A rms 90 A rms 135 A rms 180 A rms 270 A rms 360 A rms
System input
** Nominal voltage 380 to 415 VAC -15%, +10%
Nominal frequency 50 Hz , 60 Hz, +/- 8%
Number of phases of phases 3 phases with or without neutral
Operation is possible with single-phase or unbalanced loads
Current transformers Range from 300/1 to 4000/1, split or solid
Technical characteristics
Compensated harmonic currents H2 to 50, harmonic compensation if configurable
Harmonic attenuation rate THDI load /THDI system less than 10, at the nominal rating of the equalizer
Correction of Cos ø Lagging or Leading, up to 1.0
Response time < 40 ms
Overload Limitation of the nominal current, possibility of continuous operation with current limitation
Inrush current < 2 x the nominal peak current
Heat losses 1000 W 1300 W 2100 W 2600 W 4200 W 5200 W
Number of units in configuration 1 1 1 1 2 2
Acoustic noise (ISO 3746) <55 dBA <60 dBA <65 dBA
Color RAL 9002 (Grey White)
Environmental conditions
Operating temperature 0 to 40°C continuous, <25°C recommended
Storage Temperature -20 to 45°C
Relative humidity 0 to 95 % without condensation
Operating altitude < 1000 m
Reference technical standards
Safety EN 60950-1
Protection IP 20 conforming to EN 60529
EMC
Conducted and radiated emission EN 61000-6-4
CISPR 11 Level A
Immunity to electrostatic discharge IEC 61000-4-2
Immunity to electromagnetic fields IEC 61000-4-3
Immunity to impulse waves
Fast transient
Surge
EN 61000-4-4
EN 61000-4-5
NOTES:
* Product numbers ending in “U” are Unitary and require the option expansion kit to be connected in parallel to other AccuSine SWP
products. Product numbers ending in “P” are shipped in a parallel enabled configuration and can be connected to other AccuSine
SWP d t f hi h t d l ti U t f d t f th ti b t d i ll l f t 480 products for higher rated solutions. Up to four products, of the same rating, can be connected in parallel for up to 480 A
compensation capacity per phase.
**208 VAC voltage is supported with the field installation of an autotransformer
See the document “AccuSine SWP 20-480A Autotransformer for 208V Mains Installation Manual“ for more information
Thiết bị AccuSine Schneider
Điều khiển và trung hòa sóng hài cho tải không tuyến tính trong môi trường thương mại và công nghiệp.
Lọc sóng hài và điều khiển hệ số công suất toàn diện trong cùng 1 thết bị có công suất đến 1000KVA giúp khách hàng giảm chi phí đầu tư.
Danh mục: Sản phẩm hạ thế, Tất cả sản phẩm
Đánh giá
Chưa có đánh giá nào.